Currencies Selector

$
MCCB

Compact NSX 100B 3P 40A

50.00$
40.00$
SKU : 5000
Brand : Schneider Electric

Compact NSX 100B 3P 16A Schneider LV429550 : ឌីហ្សង់ទ័រខ្នាតធំ MCCB Schneider Icu 25kA, Ics 25kA, ការពារពីកំដៅ,ស្តង់ដារ 60947-2

លក្ខណះពិសេស MCCB Compact NSX100B 3P 16A Datasheet / Catalogue Download

Range                                                           Compact
Product name                                              Compact NSX
Product or component type                          Circuit breaker
Device short name                                       Compact NSX100B
Device application                                         Distribution
Poles description                                          3P
Protected poles description                          3t
Network type                                                 AC
Network frequency                                        50/60 Hz
[In] rated current                                           100 A ( 40 °C )
[Ui] rated insulation voltage                          800 V AC 50/60 Hz [Uimp] rated impulse withstand voltage       8 kV
[Ue] rated operational voltage                       690 V AC 50/60 Hz
Breaking capacity code                                 B (25 kA) AC
Breaking capacity                                        25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
  20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity             Ics 20 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
  Ics 25 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 
  Ics 40 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 
  Ics 7.5 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation                                   Yes conforming to EN 60947-2 Yes conforming to IEC 60947-2
Utilisation category                                      Category A
Trip unit name                                               TM-D
Trip unit technology                                      Thermal-magnetic
Trip unit protection functions                         LI
Trip unit rating                                               100 A ( 40 °C )
Protection type                                              Overload protection (thermal) L
  Short-circuit protection (magnetic) I
Pollution degree                                            3 conforming to IEC 60664-1
Complementary  
Control type                                                  Toggle
Mounting mode                                            Fixed
Mounting support                                          Backplate
Upside connection                                        Front
Downside connection                                   Front
Mechanical durability                                    50000 cycles
   
Electrical durability                                        10000 cycles 690 V In conforming to IEC 60947-2 
  20000 cycles 690 V In/2 conforming to IEC 60947-2
  30000 cycles 440 V In conforming to IEC 60947-2
  50000 cycles 440 V In/2 conforming to IEC 60947-2
   
Connection pitch                                           35 mm
Local signalling                                             Positive contact indication 
Long time pick-up adjustment type Ir            Adjustable
Long time pick-up adjustment range             0.7...1 x In 
Long time delay adjustment type                  Fixed
[Tr] long-time delay adjustment range          15 s 6 x Ir
  120...400 s 1.5 x In
Short-time pick-up adjustment type Isd         Fixed
[Isd] short-time pick-up adjustment range 800 A
Short-time delay adjustment type                Fixed
Height                                                           161 mm
Width                                                             105 mm
Depth                                                            86 mm
Product weight                                              2.05 kg
Environment  
Overvoltage category                                    Class II
Electrical shock protection class                   Class II
Standards                                                     EN/IEC 60947
Product certifications                                    CCC Marine EAC
IP degree of protection                                 IP40 conforming to IEC 60529
IK degree of protection                                 IK07 conforming to IEC 62262 
Ambient air temperature for operation          -35...70 °C
Ambient air temperature for storage             -55...85 °C
Offer Sustainability  
Sustainable offer status                                Green Premium product
RoHS (date code: YYWW)                           Compliant
Schneider Electric declaration of conformity  
REACH                                                         Reference not containing SVHC above the threshold 
  Reference not containing SVHC above the threshold
Product environmental profile                       Available
Product end of life instructions                      Available